Safety Solenoid Valve – Normally Open

General Details
Normally open/closed safety solenoid valves with manual reset. e closing/opening function is electrically activated.
is type of device connected to one or more methane gas detectors and/or carbon monoxide detectors, is suitable for performing locking operations on the gas line.
An incorporated ne mesh lter protects the valve seat and disc as well as downstream components and prevents dirty contamination (except brass models). All components are desgned to withstand any mechanical, chemical and thermal condition occuring during typical service. Eective impregnation and surface treatments have been used to improve mechanical sturdiness, sealing and resistance to corrosion of the components.
Valves are 100% tested by computerized testing machineries and are fully warranted.

electrovalve_tabel_ro

Technical Info
Connections :
Gas threaded ISO 7/1 from Rp3/8 to Rp2 ½
Flanged PN16 – ISO 7005 from DN40 to DN300
Voltage rating: 230 VAC 50/60 Hz
110 VAC 50/60 Hz
24 VAC; 24 VDC
12 VDC
Voltage tolerance: -15% / +10%
Working temperature: -15°C/+60°C
Max. operating pressure: 600 mbar (60 kPa)
6 bar (600 kPa)
Closing time: < 1 sec.
Filter (except brass models): 600 μm, metal mesh
Protection grade: IP 54 (EN 60529)
Cable gland: PG 9
Coil winding insulation: Clasa H (200°C)
Coil thermal resistance: Clasa F (155°C)
Materials in contact with gas: Aluminum alloy, Brass,
Stainless steel, Plated steel, Anaerobic adhesive,